Customization: | Available |
---|---|
Type: | Precision Air Conditioner |
Air Tube Material: | Galvanized Sheet |
Still deciding? Get samples of US$ 6142/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
constant temperature and humidity precision air conditioner spec | ||||||||||||||||||
Model GT-HFM-() | 07 | 12 | 15 | 18 | 20 | 24 | 27 | 30 | 35 | 40 | 50 | 55 | 60 | 70 | 80 | 90 | ||
Total cooling capacity | kW | 7.5 | 12.6 | 15.3 | 18.6 | 21.8 | 24.2 | 27.5 | 31.8 | 36.5 | 42.1 | 49.1 | 54.1 | 61 | 71.6 | 81.4 | 93.6 | |
Sensible cooling capacity | kW | 6.9 | 11.7 | 14.1 | 17.4 | 20.2 | 22.4 | 25 | 29.5 | 33.8 | 38.4 | 44.3 | 49.8 | 55.5 | 65.1 | 74.7 | 85.1 | |
Electric heating | kW | 3 | 6 | 6 | 9 | 9 | 9 | 12 | 15 | 15 | 18 | 18 | 18 | 24 | 24 | 30 | 30 | |
Air volume 2* | m3/h | 1800 | 3250 | 4100 | 5200 | 5400 | 6600 | 7500 | 9000 | 10500 | 11500 | 13000 | 15500 | 18000 | 20500 | 22000 | 25000 | |
Outlet air pressure 2* | Pa | 25 | 25 | 25 | 50 | 50 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 100 | 100 | 125 | 125 | |
Noise 3* | dB(A) | 54 | 54 | 55 | 56 | 56 | 56 | 56 | 56 | 56 | 58 | 58 | 58 | 58 | 58 | 60 | 60 | |
Temperature control range and accuracy | C | 18~28,±1 | ||||||||||||||||
Humidity control range and accuracy | % | 45~70,±5 | ||||||||||||||||
Power | 3N-380V-50Hz | |||||||||||||||||
Input power 4* | kW | 6 | 11 | 12.6 | 16.8 | 17.5 | 19 | 23.9 | 28.9 | 30 | 38.2 | 39.6 | 40.7 | 52.3 | 56.7 | 66.8 | 74.8 |