Customization: | Available |
---|---|
Type: | Marine Type Package Air Conditioner |
Air Tube Material: | Plastics |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Project: | Type: | Chilled water AHU | |||||
Location | Deck 7 | Serving: | FWD Wheelhouse | ||||
Type | Centrifugal, backward curve | Mixing section | |||||
Air discharge position | Front | ||||||
Return air position | Back | ||||||
Fan brand | KRUGER/Nicotra | ||||||
Fan model | |||||||
Drive method | V-Belt Drive | ||||||
Anti vibration | Spring Isolater | ||||||
Air flow | CMH | 5510 / 2755 (2-Speed) | |||||
External Static Pressure | Pa | 400 | |||||
Description | Tubular tube with fin type of SS304 | Electric Heating | |||||
Capacity | KW | 35kW (2-stage) | |||||
Power supply | 440V/3PH/60HZ | ||||||
Type | Atomised mist | Humidification | |||||
Power supply | 230V/1P/60hz or 440V/3P/60hz | ||||||
Capacity | litre/hr | 20 l/hr | |||||
Washable Pre filter | Disposable type | Filter | |||||
Type | Primary type: EU5 | ||||||
Power supply | 440V/3PH/60HZ | Fan motor | |||||
Enclosure class | IP55, Insulation F | ||||||
Brand | ABB/Siemens | ||||||
Space heater | Included | ||||||
Fan speed | rpm | ||||||
Motor power | KW | ||||||
Motor speed | rpm | 1390 | |||||
Pole | 4 | ||||||
Cooling capacity | KW | 59.0 | Cooling coil | ||||
Inlet/outlet water | ºC | 7 / 12 | |||||
Water Flow | m3/h | ||||||
Pipe connection | |||||||
On coil air temp | ºCDB | 26degC / 72%RH | |||||
Off coil air temp | ºCDB | 13degC / 90%RH | |||||
Construction | Copper tubes with heresite coated aluminum fins, stainless steel frame SS304 | ||||||
Material | stainless steel sheet SS304 drain tray, thickness 1.0mm | Drain tray | |||||
Connection | Both side,DN32 | ||||||
Hot dip galvanized steel ceiling mounted angle bar | Unit foundation | ||||||
Multiple side | Access door | ||||||
Aluminium Alloy Frame ,50mm non-flameable PU Insulation,Inside: Powder coated sheet external 1.0mmthick, internal 1.0mmthick | Frame and panel | ||||||
mm | H<750mm | Dimensions(L*W*H) | |||||
kg | Net weight | ||||||
kg | Gross weight | ||||||
Remarks: | |||||||
All wiring and cable to be suitable for marine application | |||||||
All wiring to be routed to termination box of IP55 at AHU | |||||||
Air flow pressure switch to be provided | |||||||
AHU interior lighting to be provided | |||||||
AHU window port to be provided | |||||||
Electric heater to include overload protection and adjustable overheating protection | |||||||
Inlet/discharble manual dampers to be provided | |||||||
Electrical control panel to be provided | |||||||
Electrical control including hourly run meter, remote alarm signal, remote on/off capability, temperature control for heating, cooling, humidity control |