Customization: | Available |
---|---|
Type: | Package AC Unit |
Air Tube Material: | Galvanized Sheet |
Still deciding? Get samples of US$ 2000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | WRF12ZA | WRF 15ZA | WRF18ZA | WRF24ZA | WRF30ZA | WRF 35ZA | ||||
WF12ZA | WF 15ZA | WF18ZA | WF24ZA | WF30ZA | WF 35ZA | |||||
Cooling capacity | kW | 12 | 15.2 | 17.5 | 24 | 30.3 | 35.6 | |||
Heating capacity | kW | 13.2 | 16.6 | 18.4 | 26.5 | 33.3 | 37.7 | |||
Energy regulation |
% | 0,100% | 0,50,100% | |||||||
Power | 380V / 3Ph / 50HZA | |||||||||
Cooling input capacity | kW | 4.1 | 5.3 | 5.5 | 8.8 | 11.3 | 12.3 | |||
Heating input capacity | kW | 3.8 | 4.8 | 5.1 | 8.2 | 10.4 | 11.3 | |||
Start current | A | 48 | 62 | 63 | 63 | 74 | 76 | |||
Cooling running current | A | 7.4 | 9.7 | 10.2 | 16.1 | 21.2 | 23.3 | |||
Heating running current | A | 6.9 | 9.2 | 9.7 | 15.1 | 20.1 | 22.2 | |||
Throttling method |
Thermal expansion valve |
|||||||||
Cooling system | 1 | 1 | 1 | 1 | 2 | 2 | ||||
Refrigerant | R410A | |||||||||
Compressor | Compressor type | Hermetic scroll compressor |
||||||||
Qty | 1 | 1 | 1 | 1 | 2 | 2 | ||||
Condensation side |
||||||||||
Condenser | Type | Copper tube and aluminum fin | ||||||||
Qty | 1 | 1 | 1 | 1 | 1 | 1 | ||||
Drive type | Direct drive | |||||||||
Motor power | kW | 0.25 | 0.37 | 0.37 | 0.55 | 0.75 | 0.75 | |||
Air volume | m3 /h | 4600 | 7800 | 7800 | 9000 | 12600 | 12600 | |||
Evaporation side |
||||||||||
Evapotator | Type | Copper tube and aluminum fin | ||||||||
Qty | 1 | 1 | 1 | 1 | 1 | 1 | ||||
Motor power | kW | 0.32 | 0.37 | 0.45 | 1.1 | 1.5 | 2.2 | |||
Air volume | m3 /h | 2100 | 2600 | 3400 | 4100 | 5200 | 6300 | |||
Drive type | Direct drive | Pulley | ||||||||
Static pressure(Pa) | 100 | 100 | 100 | 200 | 200 | 250 | ||||
Filter | Aluminum filter G3 | |||||||||
Noise dB(A) | 67 | 67 | 68 | 71 | 72 | 72 | ||||
Refrigerant filling volume(kg) | 3.1 | 3.1 | 4.3 | 2x3.1 | 2x3.1 | 2x4.3 | ||||
External dimension | L | mm | 1410 | 1410 | 1410 | 1978 | 1978 | 1978 | ||
W | mm | 1100 | 1100 | 1100 | 1175 | 1175 | 1175 | |||
H | mm | 1095 | 1095 | 1095 | 1095 | 1095 | 1095 | |||
Weight | kg | 240 | 260 | 290 | 420 | 480 | 500 |
package ac unit application:
The units are widely used in the air system of many inductries like mechanical ,electronic, textile,medical,chemical,energy and foo inductries ,etc. the units are also ideal solution for restaurants, office buildings,hospitals,theaters,supermarkets and palaestra.
package ac unit structure diagram
1. Conventional
2. Technical purification
3. Heat recovery type
rooftop air conditioners factory